Deutz INDUSTRIAL ENGINES
Deutz F3L912
FL 912
Deutz F3L912 FL 912 diesel engine. Air-cooled legacy generator-drive model for 50/60 Hz sets. Source-backed mechanical ratings include 24/26 kWm at 1500 rpm and 28/30 kWm at 1800 rpm.
Standby Power
34 kVA
Electrical Output
27 kWe
Cylinders / Config
L3, naturally aspirated
Displacement
2.828 L
Rated Speed
1,500 RPM
ISO 8528 Power Ratings
Power Factor: 0.8 pfkWm = mechanical engine shaft power · kWe = electrical output · kVA = apparent electrical power.
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 24 | 21.6 | 27 |
| Standby | 26 | 23.4 | 29.2 |
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 28 | 25.2 | 31.5 |
| Standby | 30 | 27 | 33.8 |
Mechanical & Electrical Specifications
| Brand | Deutz |
| Model | F3L912 |
| Series | FL 912 |
| Configuration | L3, naturally aspirated |
| Cylinders | 3 |
| Displacement | 2.828 L |
| Fuel Type | Diesel |
| Ignition Type | Compression Ignition |
| Cooling Method | Air-Cooled |
| Emissions Standard | Unregulated |
| Country of Origin | Germany |
Frequently Asked Questions
What is the power output of the Deutz F3L912?
The Deutz F3L912 is rated at 29 kVA standby / 27 kVA prime at 50 Hz (1,500 rpm); and 34 kVA standby / 32 kVA prime at 60 Hz (1,800 rpm).
Does the F3L912 run at 50 Hz or 60 Hz?
The Deutz F3L912 is available for both 50 Hz (1,500 rpm) and 60 Hz (1,800 rpm).
What fuel does the Deutz F3L912 use?
The Deutz F3L912 is a diesel generator-set engine.
What is the displacement and cylinder configuration of the F3L912?
The Deutz F3L912 is an inline-3 (3-cylinder) engine with a displacement of 2.828 L.