Perkins INDUSTRIAL ENGINES
In ProductionPerkins 4008TAG1A
4000 Series
The Perkins 4008TAG1A is a 30.6-litre V8 diesel engine for generator sets, rated at 1,003 kVA / 802 kWe standby power at 1,500 RPM (50 Hz). It is a liquid-cooled engine built in United Kingdom.
Standby Power
1003 kVA
Electrical Output
802 kWe
Cylinders / Config
V8
Displacement
30.6 L
Rated Speed
1,500 RPM
ISO 8528 Power Ratings
Power Factor: 0.8 pfkWm = mechanical engine shaft power · kWe = electrical output · kVA = apparent electrical power.
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 808.9 | 728 | 910 |
| Standby | 891.1 | 802 | 1002.5 |
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 785.6 | 707 | 883.8 |
| Standby | 866.7 | 780 | 975 |
Mechanical & Electrical Specifications
| Brand | Perkins |
| Model | 4008TAG1A |
| Series | 4000 Series |
| Configuration | V8 |
| Cylinders | 8 |
| Displacement | 30.6 L |
| Fuel Type | Diesel |
| Ignition Type | Compression Ignition |
| Cooling Method | Liquid-Cooled |
| Emissions Standard | Unregulated |
| Country of Origin | United Kingdom |
Frequently Asked Questions
What is the power output of the Perkins 4008TAG1A?
The Perkins 4008TAG1A is rated at 1,003 kVA standby / 910 kVA prime at 50 Hz (1,500 rpm); and 975 kVA standby / 884 kVA prime at 60 Hz (1,800 rpm).
Does the 4008TAG1A run at 50 Hz or 60 Hz?
The Perkins 4008TAG1A is available for both 50 Hz (1,500 rpm) and 60 Hz (1,800 rpm).
What fuel does the Perkins 4008TAG1A use?
The Perkins 4008TAG1A is a diesel generator-set engine.
What is the displacement and cylinder configuration of the 4008TAG1A?
The Perkins 4008TAG1A is a V8 (8-cylinder) engine with a displacement of 30.6 L.
Is the Perkins 4008TAG1A still in production?
Yes — the Perkins 4008TAG1A is a current production model.
Is a datasheet available for the 4008TAG1A?
Yes — an official Perkins datasheet for the Perkins 4008TAG1A can be downloaded from this page.