Scania INDUSTRIAL ENGINES
In ProductionScania DC16 093A 02-52
DC16 Series
Scania DC16 093A 02-52 16.4L 8-cylinder diesel engine for generator sets. Unregulated emissions.
Standby Power
613 kVA
Electrical Output
490 kWe
Cylinders / Config
L8
Displacement
16.4 L
Rated Speed
1,500 RPM
ISO 8528 Power Ratings
Power Factor: 0.8 pfkWm = mechanical engine shaft power · kWe = electrical output · kVA = apparent electrical power.
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 493.3 | 444 | 555 |
| Standby | 544.4 | 490 | 612.5 |
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 488.9 | 440 | 550 |
| Standby | 540 | 486 | 607.5 |
Mechanical & Electrical Specifications
| Brand | Scania |
| Model | DC16 093A 02-52 |
| Series | DC16 Series |
| Configuration | L8 |
| Cylinders | 8 |
| Displacement | 16.4 L |
| Fuel Type | Diesel |
| Ignition Type | Compression Ignition |
| Cooling Method | Liquid-Cooled |
| Emissions Standard | Unregulated |
| Country of Origin | Sweden |
Frequently Asked Questions
What is the power output of the Scania DC16 093A 02-52?
The Scania DC16 093A 02-52 is rated at 613 kVA standby / 555 kVA prime at 50 Hz (1,500 rpm); and 608 kVA standby / 550 kVA prime at 60 Hz (1,800 rpm).
Does the DC16 093A 02-52 run at 50 Hz or 60 Hz?
The Scania DC16 093A 02-52 is available for both 50 Hz (1,500 rpm) and 60 Hz (1,800 rpm).
What fuel does the Scania DC16 093A 02-52 use?
The Scania DC16 093A 02-52 is a diesel generator-set engine.
What is the displacement and cylinder configuration of the DC16 093A 02-52?
The Scania DC16 093A 02-52 is an inline-8 (8-cylinder) engine with a displacement of 16.4 L.
Is the Scania DC16 093A 02-52 still in production?
Yes — the Scania DC16 093A 02-52 is a current production model.
Is a datasheet available for the DC16 093A 02-52?
Yes — an official Scania datasheet for the Scania DC16 093A 02-52 can be downloaded from this page.