Scania INDUSTRIAL ENGINES
In ProductionScania DC16 093A 02-54
DC16 Series
Scania DC16 093A 02-54 16.4L 8-cylinder diesel engine for generator sets. Unregulated emissions.
Standby Power
720 kVA
Electrical Output
576 kWe
Cylinders / Config
L8
Displacement
16.4 L
Rated Speed
1,500 RPM
ISO 8528 Power Ratings
Power Factor: 0.8 pfkWm = mechanical engine shaft power · kWe = electrical output · kVA = apparent electrical power.
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 568.9 | 512 | 640 |
| Standby | 627.8 | 565 | 706.3 |
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 578.9 | 521 | 651.3 |
| Standby | 640 | 576 | 720 |
Mechanical & Electrical Specifications
| Brand | Scania |
| Model | DC16 093A 02-54 |
| Series | DC16 Series |
| Configuration | L8 |
| Cylinders | 8 |
| Displacement | 16.4 L |
| Fuel Type | Diesel |
| Ignition Type | Compression Ignition |
| Cooling Method | Liquid-Cooled |
| Emissions Standard | Unregulated |
| Country of Origin | Sweden |
Frequently Asked Questions
What is the power output of the Scania DC16 093A 02-54?
The Scania DC16 093A 02-54 is rated at 706 kVA standby / 640 kVA prime at 50 Hz (1,500 rpm); and 720 kVA standby / 651 kVA prime at 60 Hz (1,800 rpm).
Does the DC16 093A 02-54 run at 50 Hz or 60 Hz?
The Scania DC16 093A 02-54 is available for both 50 Hz (1,500 rpm) and 60 Hz (1,800 rpm).
What fuel does the Scania DC16 093A 02-54 use?
The Scania DC16 093A 02-54 is a diesel generator-set engine.
What is the displacement and cylinder configuration of the DC16 093A 02-54?
The Scania DC16 093A 02-54 is an inline-8 (8-cylinder) engine with a displacement of 16.4 L.
Is the Scania DC16 093A 02-54 still in production?
Yes — the Scania DC16 093A 02-54 is a current production model.
Is a datasheet available for the DC16 093A 02-54?
Yes — an official Scania datasheet for the Scania DC16 093A 02-54 can be downloaded from this page.