Perkins INDUSTRIAL ENGINES
In ProductionPerkins 1206A-E70TTAG2
1200 Series
The Perkins 1206A-E70TTAG2 is a 7.0 L inline-6 diesel generator engine in the Perkins 1200 Series. It is listed for 50 Hz generator sets at 184 kWe / 230 kVA prime and 200 kWe / 250 kVA standby, making this page a focused reference for mid-range generator package sizing.
Standby Power
250 kVA
Electrical Output
200 kWe
Cylinders / Config
L6
Displacement
7 L
Rated Speed
1,500 RPM
ISO 8528 Power Ratings
Power Factor: 0.8 pfkWm = mechanical engine shaft power · kWe = electrical output · kVA = apparent electrical power.
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 204.4 | 184 | 230 |
| Standby | 222.2 | 200 | 250 |
Mechanical & Electrical Specifications
| Brand | Perkins |
| Model | 1206A-E70TTAG2 |
| Series | 1200 Series |
| Configuration | L6 |
| Cylinders | 6 |
| Displacement | 7 L |
| Fuel Type | Diesel |
| Ignition Type | Compression Ignition |
| Cooling Method | Liquid-Cooled |
| Emissions Standard | Unregulated |
| Country of Origin | United Kingdom |
Frequently Asked Questions
What is the power output of the Perkins 1206A-E70TTAG2?
The Perkins 1206A-E70TTAG2 is rated at 250 kVA standby / 230 kVA prime at 50 Hz (1,500 rpm).
Does the 1206A-E70TTAG2 run at 50 Hz or 60 Hz?
The Perkins 1206A-E70TTAG2 is rated for 50 Hz (1,500 rpm).
What fuel does the Perkins 1206A-E70TTAG2 use?
The Perkins 1206A-E70TTAG2 is a diesel generator-set engine.
What is the displacement and cylinder configuration of the 1206A-E70TTAG2?
The Perkins 1206A-E70TTAG2 is an inline-6 (6-cylinder) engine with a displacement of 7 L.
Is the Perkins 1206A-E70TTAG2 still in production?
Yes — the Perkins 1206A-E70TTAG2 is a current production model.
Is a datasheet available for the 1206A-E70TTAG2?
Yes — an official Perkins datasheet for the Perkins 1206A-E70TTAG2 can be downloaded from this page.