Perkins INDUSTRIAL ENGINES
In ProductionPerkins 1206J-E70TTAG4
1200 Series
Perkins 1206J-E70TTAG4 7.01 L L6 ElectropaK diesel engine for generator sets. At 60 Hz and 1800 RPM, Perkins publishes 208 kWm net / 180 kWe prime and 229 kWm net / 200 kWe standby. Euro Stage V / U.S. EPA Final Tier 4.
Standby Power
250 kVA
Electrical Output
200 kWe
Cylinders / Config
L6
Displacement
7.01 L
Rated Speed
1,500 RPM
ISO 8528 Power Ratings
Power Factor: 0.8 pfkWm = mechanical engine shaft power · kWe = electrical output · kVA = apparent electrical power.
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 176.7 | 159 | 198.8 |
| Standby | 194.4 | 175 | 218.8 |
| Operating Duty | kWm (Mechanical) | kWe (Electrical) | kVA (Rating) |
|---|---|---|---|
| Prime | 208 | 180 | 225 |
| Standby | 229 | 200 | 250 |
Mechanical & Electrical Specifications
| Brand | Perkins |
| Model | 1206J-E70TTAG4 |
| Series | 1200 Series |
| Configuration | L6 |
| Cylinders | 6 |
| Displacement | 7.01 L |
| Fuel Type | Diesel |
| Ignition Type | Compression Ignition |
| Cooling Method | Liquid-Cooled |
| Emissions Standard | Euro Stage V / U.S. EPA Final Tier 4 |
| Certifications | Euro Stage V, U.S. EPA Final Tier 4 |
| Country of Origin | United Kingdom |
Frequently Asked Questions
What is the power output of the Perkins 1206J-E70TTAG4?
The Perkins 1206J-E70TTAG4 is rated at 219 kVA standby / 199 kVA prime at 50 Hz (1,500 rpm); and 250 kVA standby / 225 kVA prime at 60 Hz (1,800 rpm).
Does the 1206J-E70TTAG4 run at 50 Hz or 60 Hz?
The Perkins 1206J-E70TTAG4 is available for both 50 Hz (1,500 rpm) and 60 Hz (1,800 rpm).
What fuel does the Perkins 1206J-E70TTAG4 use?
The Perkins 1206J-E70TTAG4 is a diesel generator-set engine.
What is the displacement and cylinder configuration of the 1206J-E70TTAG4?
The Perkins 1206J-E70TTAG4 is an inline-6 (6-cylinder) engine with a displacement of 7.01 L.
What emissions standard does the 1206J-E70TTAG4 meet?
The Perkins 1206J-E70TTAG4 is certified to Euro Stage V / U.S. EPA Final Tier 4 emissions standards.
Is the Perkins 1206J-E70TTAG4 still in production?
Yes — the Perkins 1206J-E70TTAG4 is a current production model.
Is a datasheet available for the 1206J-E70TTAG4?
Yes — an official Perkins datasheet for the Perkins 1206J-E70TTAG4 can be downloaded from this page.